Transient overvoltages on cable sheaths
Abstract
Transient overvoltage on the sheaths of high voltage cables with single point sheath earthing or cross bonding of the cable sheaths involve danger for the cable and the joints. The investigations of transient overvoltages in the case of a switching operation on a 110 kV single core oil filled cable with single sided sheath earthing are reported. A comparison between measured transient voltage variations and those calculated with the help of a traveling wave analyzer program shows very good agreement. The investigations showed that with single point sheath earthing, the unearthed sheath end ought to be protected against overvoltages.
- Publication:
-
NASA STI/Recon Technical Report N
- Pub Date:
- August 1983
- Bibcode:
- 1983STIN...8410448D
- Keywords:
-
- Overvoltage;
- Power Lines;
- Sheaths;
- Switching Circuits;
- Transient Loads;
- Traveling Waves;
- Computerized Simulation;
- Underground Transmission Lines;
- Wave Attenuation;