Safe Control of Grid-Interfacing Inverters with Current Magnitude Limits
Abstract
Grid-interfacing inverters allow renewable resources to be connected to the electric grid and offer fast and programmable control responses. However, inverters are subject to significant physical constraints. One such constraint is a current magnitude limit required to protect semiconductor devices. While many current limiting methods are available, they can often unpredictably alter the behavior of the inverter control during overcurrent events leading to instability or poor performance. In this paper, we present a safety filter approach to limit the current magnitude of inverters controlled as voltage sources. The safety filter problem is formulated with a control barrier function constraint that encodes the current magnitude limit. To ensure feasibility of the problem, we prove the existence of a safe linear controller for a specified reference. This approach allows for the desired voltage source behavior to be minimally altered while safely limiting the current output.
- Publication:
-
arXiv e-prints
- Pub Date:
- September 2024
- DOI:
- arXiv:
- arXiv:2409.13890
- Bibcode:
- 2024arXiv240913890J
- Keywords:
-
- Electrical Engineering and Systems Science - Systems and Control
- E-Print:
- 10 pages, 6 figures, Submitted to HICSS'58