Recovery of Power Flow to Critical Infrastructures using Mode-dependent Droop-based Inverters
Abstract
Recovery of power flow to critical infrastructures, after grid failure, is a crucial need arising in scenarios that are increasingly becoming more frequent. This article proposes a power transition and recovery strategy by proposing a mode-dependent droop control-based inverters. The control strategy of inverters achieves the following objectives 1) regulate the output active and reactive power by the droop-based inverters to a desired value while operating in on-grid mode 2) seamless transition and recovery of power flow injections into the critical loads in the network by inverters operating in off-grid mode after the main grid fails; 3) require minimal information of grid/network status and conditions for the mode transition of droop control. A framework for assessing the stability of the system and to guide the choice of parameters for controllers is developed using control-oriented modeling. A comprehensive controller hardware-in-the-loop-based real-time simulation study on a test-system based on the realistic electrical network of M-Health Fairview, University of Minnesota Medical Center, corroborates the efficacy of the proposed controller strategy.
- Publication:
-
arXiv e-prints
- Pub Date:
- January 2021
- DOI:
- 10.48550/arXiv.2102.00046
- arXiv:
- arXiv:2102.00046
- Bibcode:
- 2021arXiv210200046C
- Keywords:
-
- Electrical Engineering and Systems Science - Systems and Control