Power system oscillations under a large disturbance often exhibit distorted waveforms as captured by increasingly deployed phasor measurement units. One cause is the occurrence of a near-resonance condition among several dominant modes that are influenced by nonlinear transient dynamics of generators. This paper proposes an Extended Prony Analysis method for measurement-based modal analysis. Based on the normal form theory, it compares analyses on transient and post-transient waveforms to distinguish a resonance mode caused by a near-resonance condition from natural modes so that the method can give more accurate modal properties than a traditional Prony Analysis method, especially for large disturbances. The new method is first demonstrated in detail on Kundur's two-area system and then tested on the IEEE 39-bus system to show its performance under a near-resonance condition.
- Publication:
-
arXiv e-prints
- Pub Date:
- March 2020
- DOI:
- 10.48550/arXiv.2003.09651
- arXiv:
- arXiv:2003.09651
- Bibcode:
- 2020arXiv200309651X
- Keywords:
-
- Electrical Engineering and Systems Science - Systems and Control
- E-Print: