Vulnerability Assessment of Large-scale Power Systems to False Data Injection Attacks
Abstract
This paper studies the vulnerability of large-scale power systems to false data injection (FDI) attacks through their physical consequences. Prior work has shown that an attacker-defender bi-level linear program (ADBLP) can be used to determine the worst-case consequences of FDI attacks aiming to maximize the physical power flow on a target line. This ADBLP can be transformed into a single-level mixed-integer linear program, but it is hard to solve on large power systems due to numerical difficulties. In this paper, four computationally efficient algorithms are presented to solve the attack optimization problem on large power systems. These algorithms are applied on the IEEE 118-bus system and the Polish system with 2383 buses to conduct vulnerability assessments, and they provide feasible attacks that cause line overflows, as well as upper bounds on the maximal power flow resulting from any attack.
- Publication:
-
arXiv e-prints
- Pub Date:
- May 2017
- DOI:
- 10.48550/arXiv.1705.04218
- arXiv:
- arXiv:1705.04218
- Bibcode:
- 2017arXiv170504218C
- Keywords:
-
- Electrical Engineering and Systems Science - Systems and Control
- E-Print:
- 6 pages, 5 figures