Applying a Formula for Generator Redispatch to Damp Interarea Oscillations Using Synchrophasors
Abstract
If an interarea oscillatory mode has insufficient damping, generator redispatch can be used to improve its damping. We explain and apply a new analytic formula for the modal sensitivity to rank the best pairs of generators to redispatch. The formula requires some dynamic power system data and we show how to obtain that data from synchrophasor measurements. The application of the formula to damp interarea modes is explained and illustrated with interarea modes of the New England 10-machine power system.
- Publication:
-
IEEE Transactions on Power Systems
- Pub Date:
- July 2016
- DOI:
- 10.1109/TPWRS.2015.2485519
- arXiv:
- arXiv:1503.06144
- Bibcode:
- 2016ITPSy..31.3119M
- Keywords:
-
- Computer Science - Systems and Control;
- Mathematics - Optimization and Control
- E-Print:
- To appear in IEEE Transactions on Power Systems, accepted September 2015