Development of New Type Gap Arrester for Earth Fault Protection in AC Feeding System
Abstract
A gap arrester is being used for ground fault protection in AC Feeding System. However there are faults in which a conventional gap arrester burns down in a normal state of circuit. We investigated the cause of the fault in which a gap arrester burns. Then, it was found out that the cause of the fault was the discharge of AC current from the surge voltage. Therefore, we developed a new type gap arrester which does not burn down. The new type gap arrester is composed of a discharge tube and a zinc oxide element which are connected in series. Unnecessary AC current discharge is prevented by this structure. The new type gap arrester is actually used at the railroad track.
- Publication:
-
IEEJ Transactions on Industry Applications
- Pub Date:
- 2006
- DOI:
- Bibcode:
- 2006IJTIA.126.1493A
- Keywords:
-
- electric railroad;
- AC feeding system;
- earth fault;
- gap arrester