Water-cooled electronics
Abstract
LHC experiments demand on cooling of electronic instrumentation will be extremely high. A large number of racks will be located in underground caverns and counting rooms, where cooling by conventional climatisation would be prohibitively expensive. A series of tests on the direct water cooling of VMEbus units and of their standard power supplies is reported. A maximum dissipation of 60 W for each module and more than 1000 W delivered by the power supply to the crate have been reached. These values comply with the VMEbus specifications.
- Publication:
-
Nuclear Instruments and Methods in Physics Research A
- Pub Date:
- January 2000
- DOI:
- 10.1016/S0168-9002(99)00880-3
- Bibcode:
- 2000NIMPA.440..213D