Thermal actuation of extinguishing systems
Abstract
A brief review of the Response Time Index (RTI) method of characterizing the thermal response of commercial sprinklers and heat detectors is presented. Measured ceiling layer flow temperature and velocity histories from a bedroom fire test are used to illustrate the use of RTI in calculating sprinkler operation times. In small enclosure fires, a quiescent warm gas layer confined by the room walls may accumulate below the ceiling before sprinkler operation. The effects of this warm gas layer on the fire plume and ceiling jet flows are accounted for by substitution of an equivalent point source fire. Encouraging agreement was found between measured ceiling jet temperatures from steady fires in a laboratory scale cylindrical enclosure put into dimensionless form based on parameters of the substitute fire source, and existing empirical correlations from fire tests in large enclosures in which a quiescent warm upper gas layer does not accumulate.
- Publication:
-
NASA STI/Recon Technical Report N
- Pub Date:
- March 1984
- Bibcode:
- 1984STIN...8425886E
- Keywords:
-
- Actuation;
- Fire Extinguishers;
- Fires;
- Temperature Effects;
- Air Flow;
- Detection;
- Flame Temperature;
- Performance Tests;
- Time;
- Engineering (General)