Late developments in the field of heat recovery
Abstract
Developments to reduce the first cost and operating expense of large building air conditioning systems, with emphasis on heat transfer are described. The 3 pipe wide range coils dissipate part of the summer cooling load directly to the outside of the building without passing thru the water chillers. Tank circuits to automatically cycle water thru storage tanks can reduce the refrigeration load about 35% during the peak day period. Means to produce above 48.9 C hot water economically for winter heating and summer dissipation of internal heat are described. A heat balance is maintained automatically to remove only the excess winter heat beyond that which can be usefully recycled or stored.