Interruption of a dry-type transformer in no-load by a vacuum circuit-breaker
Abstract
Overvoltages generated during interruption of a dry type delta-star connected transformer in no load by a vacuum breaker were studied. During interruption of inrush current 37% of the phase-to-ground overvoltages were 5 pu, and 6% 7 pu. Comparison of experimental and theoretical results using Boyle's model shows no discrepancy for inrush currents and clean overvoltages from the steady-state interruption. Overvoltages due to repetitive reignitions (not covered by Boyle's model) are higher than the calculated values during steady-state switching.