Application of ozone to eliminate tertiary treatment of wastewater used for industrial cooling
Abstract
The beneficial performance of ozone (biofouling, corrosion, and chemical scaling control), when used as the sole source of cooling water treatment for air conditioning systems, could be obtained at higher cooling water temperatures typical of industrial cooling with secondary municipal effluent (SME) used as the cooling medium was investigated. A pilot cooling system was constructed and a 6 month experimental study initiated to determine process limits, mechanisms of scaling inhibition by ozone, and to evaluate factors influencing technical/economic feasibility. It was found that, while ozone use adequately controlled corrosion and biofouling, chemical scaling could not be prevented at conditions necessary for significant economic justification. Calculations indicate that the makeup waters (SME) used will become saturated with respect to calcium phosphate at less than 2 cycles of concentration, hence, a scaling potential exists at conditions less stringent than those used in the present study.